HomeMy WebLinkAboutFile Documents.1405 Red Butte Dr.0067-2023-BCHO (7)SMOKE ALARMS AND
CARBON MONOXIDE
DETECTORS REQUIRED
THROUGHOUT DWELLING
UNIT PER CITY OF ASPEN
MUNICIPAL CODE 8.15
These plans must be kept at the
building site or inspection
delays may occur. Construction
shall conform to these plans. All
changes shall be approved by
the building official.
Field Plan Set Must Be Printed In Color
SEPARATE PERMITS ARE
REQUIRED FOR ELECTRICAL,
PLUMBING, MECHANICAL, OR
FIRE SPRINKLER WORK
SEE NOTES #1 PLANS
It should be known that this review shall
not relieve the applicant of their
responsibility to comply with the
requirements of the City of Aspen
Municipal Code. Pursuant to
Sec.26.104.050, any permit or approval
issued in error or otherwise not in
conformity with the requirements of this
Title, shall be void. Similarly, any permit
or approval issued in reliance upon or
as a result of, a materially false
statement or representation made in
the process of obtaining the permit or
development approval shall, likewise,
be void. Any person having received a
void or voidable permit or approval
shall not be relieved from having to
comply with all applicable terms and
conditions of this Title and the City shall
not be estopped from fully enforcing
same.
A4.01
2
A4.01
3
A4.01
11
A5.02
1
A5.021
1
2
2
A A
B B
1
A5.04
1
A5.04
1
A5.03
1
A5.03
1
A5.01
1
A5.01 3
3
4
4
C C
5
5
D D
4"
/
1
'
-
0
"
4"
/
1
'
-
0
"
EXISTING CHIMNEY
NEW STANDING SEAM METAL ROOF
6
6
E E
5
SNOW GUARDS
SNOW GUARDS
SCALE:A2.23 1/4" = 1'-0"
1 PROPOSED - ROOF PLAN
NOTE:
INSTALL SNOW GUARDS ABOVE ALL REQUIRED LOCATIONS:
PARKING, UTILITY METERS,WALKWAYS, AND OTHER
POTENTIALLY OCCUPIED AREAS
STANDING SEAM METAL ROOFING
FIBERGLASS-REINFORCED
CLASS 'A' UNDERLAYMENT,
VERSASHIELD OR SIM
HIGH TEMP ICE AND WATER
UNDERLAYMENT, WIP 300 HT OR
SIM
EXISTING SHEATHING TO
REMAIN
EXISTING FRAMING AND
INSULATION TO REMAIN
EXTERIOR
ATTIC
ALL LAYERS TO BE INSTALLED
PER MANUFACTURER
RECOMMENDATIONS AND ESR
REPORT REQUIRMENTS
Autodesk Docs://1405 Red Butte/2126_1405 Red Butte_Phase 1.rvtM
SCALE:A2.23 1 1/2" = 1'-0"
R1 ROOF ASSEMBLY
NOTE:
EXISTING ROOF FRAMING CANNOT SUPPORT ADDITIONAL SNOW LOADING THAT WOULD
RESULT FROM THE ADDITION OF NEW INSULATION
Snow stops required at all locations
where roofs could shed snow onto
walkways, stairs, alleys, decks, exits,
utilities and meters, emergency escape
and rescue opening window wells, or
adjacent properties - IBC 1513/COA
8.20.020(z).
Heat trace/tape must be self-regulating
type cable and must include automatic
controls and timer capable of turning
off the system when the outdoor
temperature is above 50 degrees and
during daylight hours.
luisp
08/02/2023ZONING
SNOWMELT SYSTEM AND EQUIPMENT MANDATORY REQ'S
All snowmelt systems shall meet the following:
- Any portions in the Right of Way must be on a separate zone. A ROW permit
and Permanent Encroachment License are required.
- R10 insulation shall be installed under the area to be snowmelted or R5 insulation
shall be installed under the slab edges. (Ordinance 11 Series 2011)
- Automatic controls installed for system shut off when pavement temperature is above
50°F and no precipitation is falling. (2015 IECC R403.9 and C403.2.4.5)
- Automatic or manual controls installed for system shut off when outdoor temperature
is above 40°F. (2015 IECC R403.9 and C403.2.3.5)
- Inspection by testing hydrostatically at 1.5 times max system design pressure, but not
less than 100psi, for 15 minutes. (2015 IMC 1208.1)
08/04/2023
linzhid
0067-2023-BCHO
BORTZ NEIL K GRANTOR TRUST #2
1405 RED BUTTE DR
273501302010
Master permit under 2015 code, so
change order will fall under 2015, as
well.
No sub-electrical permit or REMP
required
External Energy Use Approved
RREMP CREMP
PERMIT #:0067-2023-BCHO DATE:_8/9/23_
SNOWMELT:________141.7 sq ft___________
POOL: _________N/A_________________
SPA: ________N/A__________________
OFFSET:_________0.74 kW_______________
REMP SHEET: ______N/A________________
REVIEWED BY: ____LD__________________
SNOWMELT SYSTEM AND EQUIPMENT MANDATORY REQ’S.
All snowmelt systems shall meet the following:
-Any portions in the Right of Way must be on a separate zone. A ROW
permit and Permanent Encroachment License are required.
-R10 insulation shall be installed under the area to be snow melted or R5
insulation shall be installed under and at the slab edges. (Ordinance 11
Series 2011)
-Automatic controls installed for system shut off when pavement
temperature is above 50°F and no precipitation is falling. (2009 IECC
Sec. 403.8 & 503.2.4.5)
-Automatic or manual controls installed for system shut off when outdoor
temperature is above 40°F. (2009 IECC Sec. 403.8 & 503.2.4.5)
-Inspection by testing hydrostatically at 1½ times max system design
pressure, but not less than 100psi, for 15minutes. (2009 IMC Sec.
1208.1)
MINIMUM BOILER AFUE: ____95%________
X