Architectural Engineering Consultants, Inc.
Mechanical, Electrical, & Lighting Design Services
An Office with LEEDTTMM Accredited Professionals
40801 US Hwy 6 & 24, Suite 214, Eagle-Vail, CO 81620 Post Office Box 8489, Avon, CO 81620
phone: 970-748-8520 email: stan@aec-vail.com web: www.aec-vail.com
April 30, 2021
Will Otte
Rowland + Broughton
1830 Blake St.
Denver, CO 80202
Re: Shuford Residence
Will,
This document is intended to show compliance of the remodel construction residence located at 621 W.
Francis St. in Aspen, CO with the 2015 International Energy Conservation Code (2015 IECC). We
propose to follow the prescriptive requirements for alterations approach per sections R503.1-R503.2 of
the 2015 IECC.
The project is an existing residence with a total floor area of 3,478 sf. For heat load calculations, please
refer to the following pages of this document. The heat load calculations are performed using the Carrier
Hourly Analysis Program and provides a more detailed and accurate load than Manual J. A dewpoint
calculation is not included in these permit documents, as the roof assembly meets the requirements of
section R806.5 of the 2015 IRC.
Building Envelope
The following table lists the mandatory minimum insulation and fenestration requirements for the project
in climate zone (7). All new or altered assemblies will meet the following requirements.
Fenestration
U-factor
Skylight
U-factor
Ceiling
R-value
Wood frame
wall R-value
Floor
R-value
Basement
wall R-value
Slab R-
value
Code
Minimums
0.28 (1) 0.55 (2) (3) 38 (4) 15/19 10, 4 ft
Notes: 1) Fenestration SHGC requirements do not apply in climate zone (7)
2) R-49 cavity insulation in new or insulation sufficient to fill the existing framing cavity
3) U-0.045 in new or insulation sufficient to fill the existing framing cavity
4) Or insulation sufficient to fill the framing cavity, R-19 minimum
Sincerely,
Mark Sorensen
05/09/2021
8/12/21
MCG/DAM
Zone Sizing Summary for Duplex
Project Name: 20075 - 621 W Francis St 04/30/2021
Prepared by: AEC 02:48PM
Air System Information
Air System Name Duplex
Equipment Class UNDEF
Air System Type SZCAV
Number of zones 1
Floor Area 3495.0 ft²
Location Aspen, Colorado
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM Sum of space airflow rates
Space CFM Individual peak space loads
Calculation Months Jan to Dec
Sizing Data Calculated
Zone Sizing Data
Maximum Design Minimum Time Maximum Zone
Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (MBH)(CFM)(CFM)Load (MBH)(ft²)CFM/ft²
Zone 1 66.7 5406 5406 Aug 1500 57.4 3495.0 1.55
Zone Terminal Sizing Data
No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows
Cooling Time Air Heating Floor
Zone Name / Sensible of Flow Load Area Space
Space Name Mult.(MBH)Load (CFM)(MBH)(ft²)CFM/ft²
Zone 1
100 - LIVING ROOM B 1 6.4 Nov 1500 470 5.7 530.0 0.89
101 - MUDROOM 1 1.8 Nov 1400 131 2.1 115.0 1.14
102 - LAUNDRY 1 1.4 Jul 1700 104 1.1 55.0 1.88
103 - POWDER B 1 0.1 Jul 1500 10 0.1 20.0 0.48
104 - ENTRY 1 1.4 Jul 1500 155 3.7 105.0 1.48
105 - BEDROOM 1B 1 2.1 Jul 1700 157 2.5 180.0 0.87
106 - BATHROOM 1B 1 0.3 Jul 1500 19 0.1 40.0 0.48
107 - BEDROOM 2B 1 1.9 Jul 1500 140 2.4 180.0 0.78
108 - BATHROOM 2B 1 0.5 Jul 1700 35 0.8 40.0 0.89
109 - MECHANICAL 1 0.5 Jul 1500 75 1.8 55.0 1.37
200 - LIVING ROOM A 1 21.0 Oct 1500 1540 7.8 775.0 1.99
201 - BEDROOM 1A 1 2.5 Jul 1700 182 2.5 180.0 1.01
202 - BATHROOM 1A 1 0.3 Jul 1500 19 0.1 40.0 0.48
203 - BEDROOM 2A 1 2.2 Jul 1500 164 2.4 180.0 0.91
204 - BATHROOM 2A 1 0.5 Jul 1700 36 0.6 40.0 0.89
205 - POWDER A 1 0.3 Sep 1500 19 0.3 25.0 0.77
300 - MASTER BEDROOM 1 14.7 Sep 1400 1079 10.8 380.0 2.84
301 - OFFICE 1 3.3 Jul 1700 244 1.9 75.0 3.25
302 - STAIRS 1 2.7 Jul 1400 198 2.6 145.0 1.37
303 - MASTER BATH 1 5.1 Jul 1500 373 5.7 225.0 1.66
304 - MASTER WC 1 0.2 Jul 1200 15 0.2 20.0 0.74
305 - MASTER CLOSET 1 3.2 Jul 1700 238 2.3 90.0 2.64
Hourly Analysis Program v4.50 Page 1 of 1
05/09/2021
8/12/21
MCG/DAM
OUTDOOR TEMPERATURE -15 °F OUTDOOR TEMPERATURE 88 °F
INDOOR TEMPERATURE 70 °F INDOOR TEMPERATURE 75 °F
TOTAL HEAT LOSS 57,398 BTU/HR SENSIBLE HEAT GAIN 72,478 BTU/HR
LATENT HEAT GAIN 2,406 BTU/HR
TOTAL HEAT GAIN 74,884 BTU/HR
MANUAL J DESIGN CONDITIONS
WINTER DESIGN CONDITIONS SUMMER DESIGN CONDITIONS