St. Regis Aspen Spa Remodel
Project: 22209.00 – RAKxa Aspen Spa
Subject: Fire Protection Letter
Date: 19 April 2023
To whom this may concern,
This letter is to state that there will be no damage to the existing fire rated assemblies as part of the Interior
remodel for St Regis Spa.
Property: St. Regis Hotel
Area of Remodel: Lower Level Spa
Construction Type: 1A
The proposed spa remodel will include minor demolition on non-bearing interior partitions and new finishes
throughout including the replacement of existing decorative lighting in ceiling. Per IBC Table 601,a Type 1A
construction requires no fire rating for nonbearing interior partitions but does require floor assemblies to be 2
hour fire rated. The existing floor/ceiling assembly as seen in previous remodel construction document plan sets,
and as shown below, shows the assembly as a 2 Hour fire rated post tension concrete slab.
Existing Floor/Ceiling Assembly Detail:
06/08/2023
07/25/2023
jimp
Page 2 of 2
Reference Table 601:
The interior remodel of the Spa is proposing replacement of finishes and decorative light fixtures, in their current
location. Both of these will affect the finish layer of the floor/ ceiling assembly but not penetrate the existing
concrete assembly.
Please reach out with any questions.