HomeMy WebLinkAboutordinance.council.086A-76RECORD OF PROCEEDINGS
100 Leaves
ORDINANCE NO. ~
(Series of 197~)
AN ORDINANCE AMENDING THE UNIFORM BUILDING AND
UNIFORM FIRE CODES SO AS TO REQUIRE THE INSTALLATION
OF FIRE ALARM SYSTEMS IN EVERY APARTMENT HOUSE,
LODGING HOUSE, DORMATORY, CONVENT, ~ONASTERY,
ROOMING HOUSE, CONDOMINIUM OR HOTEL, TWO STORIES
OR MORE IN HEIGHT AND CONTAINING MORE THAN FOUR (4)
APARTMENTS OR GUEST ROOMS; FURTHER AMENDING THESE
CODES BY REQUIRING THAT WHENEVER A FIRE ALARM IS
REQUIRED, THAT BOTH AN AUDIO AND VISUAL ALARM BE
INSTALLED (MEETING CERTAIN SPECIFICATIONS); AND
REQUIRING THAT ALL SYSTEMS IN EXISTENCE ON THE
EFFECTIVE DATE OF THIS ORDINANCE BE BROUGHT INTO
CONFORMITY WITHIN ONE YEAR HEREOF
WHEREAS, the City Council of the City of Aspen on
the recommendation of the Fire Marshal, has determined to amend
the provisions of the previously adopted Uniform Building and
Uniform Fire Codes to require installation of fire alarm systems
in occupancies not heretofore required to have such a system,
and to require the addition of visual fire alarms to those
audible alarms presently required so as (1) to provide an
adequate system to alert all occupants in the event of a fire,
(2) to clearly differentiate between burglar and fire alarms,
(3) to indicate the type of system activated, (4) to locate,
for the benefit of the fire department, the position of their
connections (even though covered with snow or vegetation),
and (5) because vidio alarms demand more attention.
NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL
OF THE CITY OF ASPEN, COLORADO:
Section 1
That Section 7-141 of the Municipal Code of the
City of Aspen, Colorado, is hereby amended by the addition of
subsection (q) thereto, ?hich said subsection reads:
"(q) The Uniform Building Code is hereby amended
by the addition of subsections (e), (f) and (q) to
section 3801, which said subsections shall read as
RECORD OF PROCEEDINGS
100 Leaves
follows:
Sec. 3801 (e). A visual signal shall be required
whenever an audible alarm signal is required for
an automatic fire alarm system. The visual signal
shall meet the following requirements:
1. The light used shall be of the strobe type
producing at least one million candle power, or
or incandescent flashing type which can be plainly
seen for at least 1,500 feet in all directions
of approach.
2. Lights are to be red in color for systems
equipped with a fire department connection and
yellow in color for systems not having a fire
department connection.
3. In systems with a fire department connection
the light is to be located at least 12' above and
as directly vertical to the fire department con-
nection as possible. In systems without fire
department connection the light is to be located
so as to be visible from the nearest street.
4. A sign with the words "Fire, Call Fire Depart-
ment'' (black on a white background and large
enough to be visible from the center of the
adjacent street) shall be mounted directly above
the light.
5. The light shall not replace the audible alarm,
but is to be used in conjunction with it.
6. The visual and audio signal shall be together
on a circuit separate from all others except
exit signs.
(f) An inside audible alarm is to be installed
-2-
RECORD OF PROCEEDINGS
100 Leaves
of Aspen,
section
wherever an alarm is required by Sec. 13.307 of
the Uniform Fire Code or Sec. 3802 of the
Uniform Building Code, except in single family,
duplex, triplex and fourplex residential dwellings.
In the case of public assembly areas with an occupant
load of one hundred (100) or more persons, or where
in the opinion of the Building Official or the
Fire Marshal, the installation of an inside alarm
may result in creating panic, the alarm signal
shall be installed in an attended area, (e.g. pro-
jection booth, manager's office) from where there
can be effectuated an orderly evacuation of the
assembly area pursuant to a system approved by
the Building Official or Fire Marshal.
(g) All fire alarm systems within the City in
operation on the effective date of this ordinance
shall, within one year of said effective date,
be brought into conformance with the above require-
ments.
Section 2
That Section 7-141 of the Municipal Code of the City
Colorado, is hereby amended by the addition of sub-
(r) thereto, which said subsection reads:
"(r) The Uniform Building Code is hereby amended
by the repeal and reenactment of Section 1302(b) to
read as follows:
(b) Special Provisions. Group H Occupancies,
more than two stories in height or having more than
3000 square feet of floor area above the first story,
shall be not less than one-hour fire-resistive
construction throughout.
-3-
RECORD OF PROCEEDINGS
100 Leaves
EXCEPTION: Dwelling units within an apartment
house not over two stories in height may have
nonbearing walls of unprotected construction,
provided the units are separated from each other
and from corridors by construction having a fire-
resistance rating of not less than one hour.
Openings to such corridors shall be equipped with
doors conforming to Section 3304(h) or other equiva-
lent protection.
Every apartment house, lodging house, dormatory,
convent, monastery, rooming house, condominium or
hotel, two stories or more in height and containing
more than four dwelling units and/or guest rooms
shall have installed therein an approved fire alarm
system as specified in the amended Sec. 13.307 of
the Uniform Fire Code.
For Group H Occupancies with a Group F, Division 1
parking garage in the basement or first floor,
see Section l102(a).
For attic space partitions and draft stops see Sec-
tion 3205.
Section 3
That Section 9-3 of the Aspen Municipal Code of the
City of Aspen, Colorado, is hereby amended by the addition of
subsection (y) thereto, which said subsection reads:
"(y) Section 13.307(a) is hereby amended to read:
Every apartment house, lodging house, dormatory,
convent, monastery, rooming house, condominium, or
hotel two stories or more in height and containing
more than four apartments or guest rooms shall have
installed therein an approved automatic or manually
operated fire alarm system so designed that all
-4-
RECORD OF PROCEEDINGS
100 Leaves
OCcupants of the building may be warned simultaneously.
Section 4
That Section 9-3 of the Municipal Code of the City of
Aspen, Colorado, is hereby amended by the addition of subsection (z)
thereto, which said subsection reads:
"(z) Section 13.307 is amended by the addition of
subsections (e), (f) and (g), which said subsections
read:
(e) A visual signal shall be required wherever
an audible alarm signal is required for an auto-
matic fire alarm system. The visual signal
shall meet the following requirements:
1. The light used shall be of the strobe type
producing at least one million candle power,
or incandescent flashing type which can be
plainly seen for at least 1,500 feet in all
directions of approach.
2. Lights are to be red in color for systems
equipped with a fire department connection and
yellow in color for systems not having a fire
fire department connection.
3. In systems with a fire department connection
the light is to be located at least 12' above
and as directly vertical to the fire department
connection as possible. In systems without
fire department connection the light is to be
located so as to be visible from the nearest
street.
4. A sign with the words "Fire, Call Fire
Department" (black on a white background and
large enough to be visible from the center of
-5-
RECORD OF PROCEEDINGS
100 Leaves
the adjacent street) shall be mounted directly
above the light.
5. The light shall not replace the audible
alarms, but is to be used in conjunction with
it.
~. The visual and audio signal shall be together
on a circuit separate from all others except
exit signs.
(f) An inside audible alarm is to be installed
wherever an alarm is required by Sec. 13.307
of the Uniform Fire Code or Section 3802 of the
Uniform Building Code, except in single family,
duplex, triplex and fourplex residential dwellings.
In the case of public assembly areas with an
occupant load of one hundred (100) or more persons
or where, in the opinion of the Building Official or
the Fire Marshal, the installation of an inside
alarm may result in creating panic, the alarm sig-
nal shall be installed in an attended area (e.g.
projection booth, manager's office) from where
there can be effectuated an orderly evacuation of
the assembly area pursuant to the system approved
by the Building Official or Fire Marshal.
(g) All fire alarm systems within the City in
operation on the effective date of this ordinance
shall, within one year from said effective date,
be brought into conformance with the above
requirements.
Section 5
If any provision of this ordinance or the application
thereof to any person or circumstance is held invalid, such
invalidity shall not affect other provisions or applications of
-6-
RECORD OF PROCEEDINGS
100 Leaves
the ordinance which can be given effect without the invalid pro-
vision or application, and to this end the provisions of this
ordinance are declared to be severable.
Section 6.
A public hearing on the ordinance shall be held on
~, 1977, at 5:00 p.m. in the City Council
Chambers, Aspen City Hall, Aspen, Colorado.
INTRODUCED, READ AI~D ORDERED published as provided by
law by the City Council of the City of Aspen, Colorado, at its
regular meeting held at the City of Aspen ~he ~ day of
~~ 1977 //' ~
-- ~y~tandley III /
/Mayor
ATTEST: c
g ~tty~rcY~erS~ hauter
ATTEST:
FINALLY adopted, passed and approved on the ~day
of ~ , 1977~,
Stagy Standley III
- Hauter
City Clerk
RECORD OF PROCEEDINGS ' 100 Leajves
STATE OF COLORADO ) .-
) ss
COUNTY OF PITKIN )
~ERTIFICATE
Ordinance No. ~'~
I, Kathryn S. Hauter, City Clerkof Aspen, Colorado,
do hereby certify that the above and foregoing ordinance was
introduced, read in full, and passed on~~__~
reading at a regular meeting of the City Council of the
City of Aspen or~, 197--7, and publish-
ed in the Aspen Times a weekly newspaper of general circul-
ation, published in the City of Aspen, Colorado, in its
issue of~, 197~, and was finally adopte~
and approved at a regular meeting of the City Council on
, 1977 , and ordered published as
, Series of 19~.~ , of said City, as
provided by law.
IN WITNESS WHEREOF, I have hereunto set my hand and
the seal of said City of Aspen, Colorado, this__/~
day of~, 197~ ~
~ter, ~
K ~ City