HomeMy WebLinkAboutordinance.council.012-77RECORD OF PROCEEDINGS
100 Leaves
oRD] n cs NO.
(Series of 1977)
AN ORDINANCE ADOPTING BY REFERENCE THE UNIFORM BUILDING
CODE, 1976 EDITION, TOGETHER WITH THE UNIFORM BUILDING
CODE STANDARDS, 1976 EDITION; AMENDING CERTAIN SECTIONS
OF SAID CODE; PROVIDING PENALTIES FOR THE VIOLATIONS OF
SAID CODE; AND REPEALING SECTIONS OF THE MUNICIPAL CODE
INCONSISTENT THEREWITH
WHEREAS, the City Council desires to adopt, for the
benefit of the City of Aspen, the 1976 edition of the
Uniform Building Code, to repeal existing building code
provisions, and implement recommended changes to the 1976
edition.
NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF
THE CITY OF ASPEN, COLORADO:
Section 1. Repeal of Existing Sections
That sections 7-140, 7-141, and 7-142 of Chapter 7 of
the Municipal Code of the City be repealed and reenacted
as follows:
Section 2. Adoption of the Uniform Building Code
That section 7-140 of the Municipal Code of the City of
Aspen, Colorado, is hereby repealed and reenacted to read as
follows:
"Section 7-140 Uniform Building Code Adopted.
~ursuant to the power and authority conferred by the laws of
the State of Colorado and the Charter of the City of Aspen,
Colorado, it is hereby adopted as the building code of the
City of Aspen, Colorado, by reference thereto, the Uniform
Building Code, 1976 edition (including the appendix, excepting
Chapters 13, 15, 38, 48, and 49 thereof) but excepting
Section 204 of such code concerning the board of appeals,
published by the International Conference of Building
Officials, 5360 South Workman Mill Road, Whittier, California,
RECORD OF PROCEEDINGS
100 Leaves
together with the Uniform Building Code Standards, 1976
edition, of the International Conference of Building Officials,
at the same address, all to have the same force and effect
as though set forth herein in every particular."
Section 3. Adoption of Amendments Thereto
That section 7-141 of the Municipal Code of the City of
Aspen, Colorado, is hereby repealed and reenacted to read as
follows:
"Section 7-141. Amendments
(a) The Uniform Building Code, 1976 Edition, Sec. 104(j
is hereby amended to read as follows:
'Sec. 104(j) Historic Buildings. Repairs, alterations
and additions necessary for the preservation, restoration,
rehabilitation or continued use of a building or
structure may be made without conformance to all the
requirements of this code when authorized by the
building inspector provided:
1. The building or structure has been determined
to be of historic, architectural or geographic
importance and has received historic designation
pursuant to the provisions of Article IX of
Chapter 24 of the Aspen Municipal Code; provided,
however, that the automatic inclusion of a structure
within a larger historic overlay district shall
not constitute, without more, a designation of
historic, architectural, or geographic importance
sufficient to meet the requirements of this sub-
paragraph.
2. Any unsafe conditions as described in Section 203
will be corrected in accordance with approved plans.
3. Any substandard conditions will be corrected
in accordance with approved plans.
-2-
RECORD OF PROCEEDINGS
100 Leaves
(b)
4. The restored building or structure will be
less hazardous, based on life and fire risk,
than the existing building.
The Uniform Building Code, 1976 edition, is hereby
amended by adding number eight to Section 301(b):
'Sec. 301(b) Application.
8. Be accompanied by a recent survey, plat and
legal description of the proposed building site
or property prepared by a registered land surveyor
licensed to practice in the State of Colorado at
time of application for a building permit. The
surveyor making the plat shall certify on the plat
that it is correct and that the perimeter monuments
described in it have been placed as described, after
which he shall affix his name and seal. Permanent
reference monuments shall be set and marked.
Permanent reference monuments under normal geographic
and topographic conditions shall be 3/4" nominal
iron pipe (1.05 inches O.D.) or #5 steel rebar 24
inches long with a metal or plastic cap at least
1 3/8 inches in diameter set that no more than 4
inches protrudes from the ground and mounded with
stones. Said plat should indicate the following:
(a) Type of monuments set on property corners.
(b) The location and dimensions of any easements
or rights-of-way of record or in evidence
on said property.
The above requirements shall not be mandatory for
a building permit application to reconstruct or
remodel totally within the limits of an existing
building or structure.
For improvements to be located on large tracts of
-3-
RECORD OF PROCEEDINGS
100 Leaves
(c)
(d)
land (5 acres or over) the provisions of section
301(b) shall not apply; but, evidence satisfactory
to the building official must be submitted which
shows the improvement on the property to be in
compliance with appropriate laws.'
The Uniform Building Code, 1976 edition, is hereby
amended by adding number nine to Section 301(b) which
said subsection shall read as follows:
'Sec. 301(b) Application
9. When construction is proposed in the special
flood hazard areas, be accompanied by elevations
(in relation to mean sea level) of the lowest
floor (including basement) of all new or sub-
stantially improved structures located in the
special flood hazard areas. If the lowest floor
is below grade on one or more sides, the elevation
of the floor immediately above must also be
submitted.'
Section 302(d) of the Uniform Building Code 1976 edition
is hereby amended to read as follows:
'Sec. 302(d) Expiration. Every permit issued by the
building official under the provisions of this code
shall expire by limitation and become null and void
if the building or work authorized by such permit is
not commenced within one hundred twenty (120) days from
the date of issuance of such permit. Work equal to
ten (10) percent of the valuation of the entire project
must be completed in each sixty-day period thereafter
until completion of the project or said project shall
be deemed abandoned and the permit expired. In the
event a permit shall expire, the following provisions
shall apply, namely:
-4-
RECORD OF PROCEEDINGS
100 Leaves
(e)
1. All below grade excavation done in anticipation
of construction shall be filled within thirty (30)
days of expiration such as to bring the site to a
condition comparable to that before permit issuance.
2. Any fences, railings, canopies and other pro-
tective structures placed in a public right-of-way,
and required by Chapter 44 of the Uniform Building
Code, shall be removed within ten (10) days of
expiration of a permit as well as all hazardous
conditions eliminated.
3. Before such work can be recommenced a new permit
shall be first obtained so to do. Such permit shall
issue for a permit fee equal to one-half the amount
required for a new permit for such work provided no
changes have been made or will be made in the plans
and specifications for such work, and provided
further that the work has not been abandoned for a
period exceeding one year.
4. The provisions of subparagraph 3 to the contrary
notwithstanding, no permit shall reissue for any
construction or activity prohibited by law at the
time of the application for reissuance.
Whenever there are practical difficulties or unnecessary
hardships in the way of carrying out the strict letter
of this section, the Board of Appeals, on appeal thereto,
may vary or modify the application of this section so
that the intent and purpose of the code will be observed,
public safety and welfare secured, and substantial
justice done.'
Table 5-C, 5-D and 17-A of the Uniform Building Code,
1976 edition, are hereby amended by changing the title
of the ninth column entitled "l-hour" to read "l-IIr,
RECORD OF PROCEEDINGS
100 Leaves
(f)
or H.?.'
Section 1302(b) of the Uniform Building Code, 1976
edition, is hereby amended to read as follows:
' (b) Special Provisions. Group R, Division 1
Occupancies, more than two stories in height or
having more than 3000 square feet of floor area
above the first story, shall be not less than one-
hour fire-resistive construction throughout.
EXCEPTION: Dwelling units within an apartment
house not over two stories in height may have
nonbearing walls of unprotected construction,
provided the units are separated from each other
and from corridors by construction having a fire-
resistance rating of not less than one hour.
Openings to such corridors shall be equipped with
doors conforming to Section 3304(h) or other equi-
valent protection.
Every apartment house, lodging house, dormatory,
convent, monastery, rooming house, condominium or
hotel, two stories or more in height and containing
more than four dwelling units and/or guest rooms
shall have installed therein an approved fire alarm
system as specified in the amended Sec. 13.307 of
the Uniform Fire Code.
For Group R, Division 1 Occupancies with a Group B,
Division 1 parking garage in the basement or first
floor, see Section l102(a).
For attic space partitions and draft stops see Sec-
tion 3205.
Mandatory Mailboxes. Within all zone districts
within the City of Aspen no multi-family structure
consisting of three or more units receiving mail
shall be constructed without the installation there-
-6-
RECORD OF PROCEEDINGS
100 Leaves
in of individual mail boxes sufficient to service
all anticipated occupants of the structure and
meeting any applicable requirements of the U.S.
Postal System for mail delivery.'
(g) Section 1501 of the Uniform Building Code, 1976 edition,
is hereby amended by deleting the words "over 6 feet high"
in Division 2 Occupancies and to read as follows:
'Sec. 1501 Division 2. Fences, tanks and towers.
Outside the city limits of Aspen a building
permit is not required for a fence under six (6)
feet high.'
(h) Chapter 15 of the Uniform Building Code, 1976 edition,
is hereby amended by adding thereto the following
as Section 1507:
'Sec. 1507 Fences and Retainin~ Walls.
1. No barbed wire or sharp fence, and no
electronically charged fence, shall be erected
or maintained within the city limits of Aspen.
2. On corner lots, no fence, retaining wall,
shrub, tree or similar obstruction shall be
erected or maintained which obstructs the
traffic vision, nor on corner lots shall any
fence, retaining wall, shrub, tree or similar
obstruction be erected or maintained which exceeds
a height of 42 inches, measured from street grade,
within 30 feet from the lot corner.
3. Any dangerous fence or obstruction in violation
of subsection 2 above, shall be removed when so
ordered by the building official.'
(i) Sections 1602(a) and (b) of the Uniform Building Code,
1976 edition, are hereby amended to read as follows:
'Sec. 1602(a) General. Buildings or structures
-7-
RECORD OF PROCEEDINGS
100 Leaves
(j)
hereafter erected, constructed, moved within or
into Fire Zone No. 1 shall be only of Type I,
Type II-F.R., Type III one-hour, or Type IV
construction, and shall meet the requirements
of this section. Except fences less than six (6)
feet in height may be of Type V construction.
Roof coverings shall be fire retardant as spe-
cified in Section 3203(e).
for repairs.
Sec. 1602(b). Alterations.
See section 104(f)
No building of Type II,
One-hour or II-N construction nor any building of
Type V construction already erected in Fire Zone
No. 1 shall hereafter be altered, raised, enlarged,
added to or moved, except as follows:
1. Changes, alterations and repairs to the
interior of such building or to the front
thereof facinga public street may be made,
provided such changes do not, in the opinion
of the building official, increase the fire
hazard of such building.
2. Roof coverings shall be fire retardant
as specified in Section 3203(e). See Section
104(f) for repairs.
3. Such building may be moved entirely out-
side the limits of Fire Zone No. 1.
4. Such building may be demolished.
Section 1603(a) and (b) of the Uniform Building Code,
1976 edition, is hereby amended to read as follows:
'Sec. 1603(a) General. Buildings or structures
hereafter erected, constructed, moved within or into
Fire Zone No. 2 shall be one of the types of con-
struction as defined in this code and shall meet
the requirements of this section. Except that any
--3--
RECORD OF PROCEEDINGS
100 Leaves
(k)
Type II, One-hour or II-N building shall only be
be permitted for Section 1501, Group M Division 1
occupancies within the city limits of Aspen. For
fire-resistive protection of exterior walls and
openings, as determined by location on property,
see Section 504 and Part V. Roof coverings shall be
fire-retardant as specified in Section 3203(e).
See Section 104(f) for repairs.
Sec. 1603(b) Alterations. No building of Type II,
One-Hour or II-N construction nor any building of
Type V construction already erected in Fire Zone No. 2
shall hereafter be altered, raised, enlarged, added
to or moved except as follows:
1. Such building may be made to conform to the
provisions of Section 2203 for Type V construction.
2. Changes, alterations and repairs to the
interior of such building or to the front thereof
facing a public street may be permitted provided
such changes do not in the opinion of the building
official, increase the fire hazard of such building.
3. Roofs of such building may be covered only
with a fire-retardant roofing as specified in
Section 3203(e). See Section 104(f) for repairs.
4. Such building may be moved entirely outside
the limits of Fire Zone No. 2.
5. Such building may be demolished.
6. Combustible finish on the outside walls may
be replaced by or covered with exterior plaster
as specified in Chapter 47.'
Section 1604 of the Uniform Building Code,
is hereby amended to read as follows:
'Sec. 1604. Any building or structure
with the requirements of
--9--
1976 edition,
complying
this code may be erected
RECORD OF PROCEEDINGS
100 Leaves
(1)
(m)
constructed, moved within or into Fire Zone No. 3,
except that any Type II, One-hour or II-N building
shall only be permitted for Section 1501, Group M
Division 1 occupancies within the city limits of
Aspen.'
Section 1705(d) (2) of the Uniform Building Code, 1976
edition, is hereby amended to read as follows:
'Sec. 1705(d) (2). Wood veneer of boards not less
than 1-inch nominal thickness or exterior type
panels not less than 3/8 inch nominal thickness may
be applied to one hundred (100) per cent of the wall
area of the first story and thirty-three and one-
third (33 1/3) per cent of the wall area for each
story above the first story provided such veneer shall
be placed either directly against fire-resistive non-
combustible surfaces or furred out from such surface
not to exceed 1 3/4" (inches) with all concealed spaces
fire stopped as provided in Section 2517(f).'
Exception No. 2 of Section 1706(2) of the uniform Building
Code, 1976 edition, is hereby amended to read as follows:
'Sec. 1706(a) Exception No. 2. In building housing
Group B occupancies equipped with automatic fire-
extinguishing systems throughout, enclosures will
not be required for openings which serve two (2)
adjacent floors and are not connected with openings
serving other floors and which are not concealed
within the building construction, provided at each
floor a draft curtain and automatic fire sprinklers
are installed around the perimeter of the opening
within two (2) feet of the draft curtain. The
draft curtain shall enclose the perimeter of the
underclosed opening and extend from the ceiling
-10-
RECORD OF PROCEEDINGS
100 Leaves
(n)
(o)
downward at least twelve (12) inches on all sides.
The spacing between sprinklers shall not exceed
six (6) feet. Provide~ however, that anything
herein to the contrary notwithstanding, with regard
to stairways which are required by this code, the
provisions of Sections 3308 and 3309 herein shall
apply.'
Section 2103(a) 5 of the Uniform Building Code, 1976
edition, is hereby amended to read as follows:
'Sec. 2103(a)5. Wood columns, beams and arches
conforming to heavy timber sizes may be used
externally where exterior walls are permitted to
be unprotected non-combustible construction or
one-hour fire-resistive non-combustible construction.'
Section 2201 of the Uniform Building Code, 1976 edition,
is hereby amended to read as follows:
'Sec. 2201. Type V buildings may be of any materials
allowed by this code.
Type V, one-hour buildings shall be of one-hour
fire-resistive construction throughout.
Type V, heavy timber construction shall conform
to section 2106 except that permanent partitions
(non-bearing exterior walls) and members of the
structural frame may be of other materials,
provided they have a fire resistance of not less
than one hour.
Materials of construction and fire-resistive
requirements shall be as specified in Chapter 17.
For requirements due to occupancy, see Chapters 6
to 15, inclusive.
For requirements in Fire Zones, see Chapter 16.
-11-
RECORD OF PROCEEDINGS
100 Leaves
(P)
(q)
Table No.
Edition,
8 at the
33-A of the Uniform Building Code, 1976
is hereby amended by addition of footnote
end of Table 33-A and 8 inserted after the
title in the fourth column. Footnote 8 to read as
follows:
,8 Not required in one or two story buildings
for the floor above or the floor below the
floor closest to grade.'
Section 3801 of the Uniform Building Code, 1976 edition,
is hereby amended by the addition of subsections (e),
(f) and (g) to read as follows:
'Sec. 3801(e). A visual signal shall be required
whenever an audible alarm signal is required for
an automatic fire alarm system. The visual signal
shall meet the following requirements:
1. The light used shall be of the strobe type
producing at least one million candle power, or
incandescent flashing type which can be plainly
seen for at least 1,500 feet in all directions
of approach.
2. Lights are to be red in color for systems
equipped with a fire department connection and
yellow in color for systems not having a fire
department connection.
3. In systems with a fire department connection
the light is to be located at least 12' above and
as directly vertical to the fire department con-
nection as possible. In systems without fire
department connection the light is to be located
so as to be visible from the nearest street.
4. A sign with the words "Fire, Call Fire Depart-
ment'' (black on a white background and large
-12-
RECORD OF PROCEEDINGS
100 Leaves
(r)
enough to be visible from the center of the
adjacent street) shall be mounted directly above
the light.
5. The light shall not replace the audible alarm,
but is to be used in conjunction with it.
6. The visual and audio signal shall be together
on a circuit separate from all others except
exit signs.
'Sec. 3801(f) An inside audible alarm is to be
installed wherever an alarm is required by Sec. 13.307
of the Uniform Fire Code or Sec. 3802 of the Uniform
Building Code, except in single family, duplex, tri-
plex and fourplex residential dwellings. In the
case of public assembly areas with an occupant load
of one hundred (100) or more persons, or where in
the opinion of the Building Official or the Fire
Marshall, the installation of an inside alarm may
result in creating panic, the alarm signal shall be
installed in an attended area, (e.g. projection booth,
manager's office) from where there can be effectuated
an orderly evacuation of the assembly area pursuant
to a system approved by the Building Official or
Fire Marshall.'
'Sec. 3801(g) All fire alarm systems within the
city in operation on the effective date of this
ordinance shall, within one year of said effective
date, be brought into conformance with the above
requirements.'
Table 43-C of the Uniform Building Code, 1976 edition,
is hereby amended by adding subsection (c) to footnote
14
to read as follows:
' (c) Topping of Grade A or B concrete not less
-13-
RECORD OF PROCEEDINGS
100 Leaves
(s)
than 1½" thickness may be substituted for the
finish flooring required in subsections (a) and (b)
above.'
Insulation Code. The Uniform Building Code, 1976 edition,
is hereby amended by the addition of Chapter 53 to such
code, which said Chapter reads as follows:
'Chapter 53 Energy Conservation and Thermal Insulation.
Purpose:
'Section 5301. This section encourages minimum
fossil fuel consumption by establishing minimum
thermal insulation standards for all occupancies
and the use of innovative energy conservation tech-
niques in buildings.
Application and Scope:
Section 5302. This Section shall apply to all
buildings and structures in use Groups A (Assembly),
E (Educational), I (Institutional), B (Business) and
R-1 (Hotels and Apartments).
Definitions:
Section 5303. For the purposes of this Section, the
following definitions shall apply:
ASHRAE is the American Society of Heating, Refriger-
ation and Air Conditioning Engineers.
DEGREE DAY is a unit, based upon temperature differ-
ence and time, used in estimating fuel consumption
and specifying nominal heating load of a building
in winter. For any one day, when the mean tempera-
ture is less than 65°F, there exist as many degree
days as there are Fahrenheit degrees difference in
temperature between the mean temperature for the
day and 65°F.
GLAZING is all transparent or translucent materials
in exterior openings.
-14-
RECORD OF PROCEEDINGS
100 Leaves
EXTERIOR WALL AREA is the gross area of wall
surfaces adjacent to heated spaces, including
glazing and doors, exposed to ambient climatic
temperatures measured for a dwelling unit or
group of units served by a heating system.
INFILTRATION is air flowing inward as through
a wall, crack, etc.
SPECIAL GLAZING is glazing which has a minimum
U factor of .70 for all glazed surfaces.
THERMAL CONDUCTIVITY (K-FACTOR) is the time rate
of heat flow through one square foot of homo-
geneous material one inch thick when there is a
temperature difference of one degree F. between
the opposite faces of the material expressed in
B.t.u./hour, square foot, degree F. per inch.
THERMAL RESISTANCE (R) is the measure of the
resistance of a material or building component
to the passage of heat. The resistance value (R)
of mass-type insulations shall not include any
value for reflective facing.
TRANSMISIVITY is the capacity of a material to
transmit radiant energy.
U FACTOR is the total heat flow through a given
construction assembly, air to air, expressed in
B.t.u./hour, per square foot, per degree F.
temperature difference.
I
U=~t
where Rt equals the sum of the resistance (R) for
the individual components of the assembly. U
factors shall be calculated according to ASHRAE
methods.
-15-
RECORD OF PROCEEDINGS
100 Leaves
UNHEATED SPACES are any spaces exposed to ambient
temperatures and not provided with a heat supply
capable of maintaining a minimum temperature of 45°F.
Section 5304. Building Insulating Material Standards
1. Ail materials used in the insulation of buildings
in order to comply with this section shall conform
with the following standards:
Cork board
Cellular glass
Expanded polystyrene insulation board
Fiberboard
Insulation Board (Urethane)
Insulation, Thermal (Perlite)
Mineral fiber, pouring or blowing
Mineral wool
Mineral wool (roof)
Perlite, Silicone treated loose fill
*Reflective, thermal
*Structural fiberboard insulating roof
deck
Vegetable or wood fiber
Vermiculite
Vermiculite, water repellant loose
fill
Wood fiber blanket
F.S. HH-I-561
F.S. HH-I-551
F.S. HH-I-524
F.S. LLL-1535 or
ASTM C-208,
Class C
F.S. HH-I-530
F.S. HH-I-574
F.S. ItH-I-1030
F.S. HH-I-521
F.S. HH-I-~26
FHA UM-37
F.S. HH-I-1252
AIMA IB Spec
F.S. HH-I-515
F.S. fill-I-585
FHA UM-30
CS-160
a. Expanded perlite: F.G. IIH-I-526 may be modified
to permit the basic material to be a mineral
substance made of rock, slag or a mixture thereof,
processed from a natural state into fiberous or
cellular form with a minimum density of 8 lbs.
per cubic foot.
b. Perimeter insulation shall comply with the FHA
test procedure, "Test Procedure to Determine
Acceptability of Perimeter Insulation for
Concrete Floor on Ground" dated June, 1956.
e
Labeling:
Mineral Fiber Insulation shall be labeled as
follows:
a. Blanket type, or combination blanket with
reflective facing:
(1) Name of manufacturer or distributor
(2) Insulation type
(3) Thermal resistance "r" value of insulation
fiber at the labeled insulation thickness.
Type I blankets with no membrane cover may
either bear a label on a partial membrane
facing or may be branded with vertical stripes.
-16-
RECORD OF PROCEEDINGS
100 Leaves
Three stripes indicates the thermal resistance
R equals 11. Five stripes indicates a resis-
tance R equals 19. No lower "R" value is
acceptable.
Types II and III blankets with non-reflective
and reflective membrane coverings respectively,
shall be labeled with appropriate "R" value of
7, 11, or 19. No lower "R" value is acceptable.
d. ?hermal resistance "R" values apply to mineral
fiber only.
2.1 Reflective Insulation
a. Blanket Type
(1) Name of manufacturer or distributor
(2) Insulation type
(3) Thermal resistance "R" value. (R value
to include single or multi-layers, foil
or kraft backed, one or both sides.)
(4) Designate direction of heat flow.
Identification labeling and marking of all
other acceptable building insulating material
shall comply with their apprpriate standard
listed in this section.
Section 5305.
and Walls
1. Ceilings:
Thermal Design Standards for ceilings
The maximum U-value for ceilings shall
be 0.05. Ail occupancies with a floor to ceiling
height in excess of twelve feet shall have a maximum
U-value for ceilings of 0.04.
2. Walls:
a. All buildings and structures in Group R-1 shall
have a maximum U-value for walls above grade of
0.05. Masonry and structural concrete walls
have a maximum U-value of .085 if the insula-
ting materials are placed on the wall's exterior.
b. All buildings and structures in Groups A, E, I,
and B shall have a maximum U-value for walls
above grade of 0.085.
c. ~alls of unheated spaces need not be insulated.
d. Basement walls below grade shall have a maximum
U-value of 0.09. This is required if the base-
-17-
RECORD OF PROCEEDINGS
100 Leaves
ment space is provided with a positive heat
supply to maintain a minimum temperature of
50OF.
Section 5306.
slabs-on-Grade
1.
Floor Section, Foundation Walls and
Ail buildings and structures in Group R-1.
a. Floors over unheated basements, crawl spaces
and garages: The maximum U-value shall be 0.05
or the walls of the foundation shall be insula-
ted to a depth of the footings with a maximum
U-value of 0.09.
b. Slabs-on-Grade: Perimeter insulation shall be
required from the top edge of the slab to a
depth of 2 feet below grade. The maximum
U-value shall be 0.1.
c. Structural concrete mats on grade shall be
required to perimeterly insulate the full
depth of the mat. The maximum U-value shall
be 0.1.
All buildings and structures in Groups A, E, I,
and B-2.
a. Floors over unheated basements, crawl spaces:
The maximum U-value shall be 0.08 or the walls
of the foundation shall be insulated to a
depth of the footings with a maximum U-value
of 0.09.
b. Slabs-on-Grade: Perimeter insulation shall
be required from the top edge of the slab to
a depth of 2 feet below grade. The maximum
U-value of the insulation shall be 0.2.
c. Structural concrete mats on grade shall be
required to perimeterly insulate the full
depth of the mat. The maximum U-value shall
-18-
RECORD OF PROCEEDINGS
100 Leaves
be 0.1.
Section 5307. Thermal Design Standards for Glazing
1. All windows, skylights, and doors shall be glazed
with insulating glass as defined in the ASHRAE
Guide - double glazing - or shall be equipped with
storm windows and storm doors. Closure providing
equivalent resistance to heat transmission will
be acceptable.
EXCEPTION: All buildings in Group B-2 may use
single glazing for display areas which are com-
pletely sealed from the interior heated spaces.
2. The total glazing area of a building shall not
exceed 14% of the total floor area for all classes
of structures.
a. Skylights shall be included as glazing areas
in these calculations.
b. South facing glazing of a buildin~ i.e.,
glazing oriented between the true bearings
165°-195°, shall not be restricted as to
total glass area upon meeting the following
requirements:
(1) South glazing shall be clear and
untreated.
(2) The total combined glazing area on
all other exposures (compass coordinates
other than 165°-195°) shall not exceed
12.3% of the total floor area for all
classes of structures. Skylights shall
be included as glazing areas.
Section 5308. Heat Distribution Equipment
1. All heating distribution duckwork and piping
running through unheated spaces shall be insulated.
-19-
RECORD OF PROCEEDINGS
100 Leaves
5306,
a. Minimum R value of duct insulation R=5.55
b. Minimum R value of piping insulation R=3.7
Section 5309. Infiltration
1. Caulking and Sealing: Exterior joints around
windows and door frames, between wall and founda-
tions, between wall and roof, between wall panels,
at penetrations of utility services through walls,
floors and roofs, and all other openings in the
exteriors envelope shall be caulked, gasketed
or otherwise weather-stripped.
2. All buildings in Groups A, E, I, and B-2 shall
be required to institute entrance sealing by
using doubled entrance systems.
Section 5310. Requirement for Day-i~ight Thermostats
All structures in groups A, E, I, and B-2 shall be
required to install day-night thermostats to reduce
heating demand during periods when building is not
occupied.
Section 5311. Design Conditions
1. All R-1 and I group structures shall use an
outside design temperature of -15°F.
2. All buildings in groups A, E, and B-2 shall use
an outside design temperature of -10°F.
Section 5312. Design Flexibility
Structures shall be exempt from sections 5304, 5305,
and 5309
5307/of Chapter 53 Energy Conservation and Thermal
Insulation upon meeting all the following requirements:
1. The maximum designed load for space heating per
square foot of heated floor space shall be as
follows:
-20-
RECORD OF PROCEEDINGS
100 Leaves
OCCUPANCY OR USE
Residential and Multi-Family
Commercial, Institutional and
Office Buildings
MAXIMUM DESIGN LOAD FOR
SPACE HEATING FOR SQUARE
FOOT OF HEATE~ FLOOR
SPACE Btuh/ft~
18 Btuh/ft2
24 Btuh/ft2
Restaurants, Auditoriums, Gymnasiums,
Theaters, Churches and all other
buildings where outside air is gov-
erned by make-up air requirements 30 Btuh/ft2
2. All calculations for determination of the design
heating load shall use the following design con-
ditions:
a. All R-1 and I structures shall use an outside
design temperature of -15°F, interior design
temperature of 70OF.
b. All buildings in groups A, E, and B-2
shall use an outside design temperature
of -10°F, interior design temperature of
70~F.
3. The building department will require calculations
by a registered professional engineer or architect
in the State of Colorado to justify compliance
with the requirements of Chapter 53. Such calcu-
lations shall conform to the procedure outlined
by the American Society of Heating, Refrigeration
Air Conditioning Engineers.
Section 5313. Exemptions to Chapter 53 Requirements
All dwelling units approved by the Colorado Division
of Housing as meeting the mobile home standard ANSI
119.1, and all R-Division 3 residences, shall be
exempt from the provisions of this Chapter 53.
Section 4. Adoption of Penalties
That Section 7-142 of the Municipal Code of the City of
-21-
RECORD OF PROCEEDINGS
100 Leaves
Aspen, Colorado, is hereby repealed and reenacted to read as
follows:
"Section 7-142 Violations and Penalties
(a) It shall be unlawful for any person,
corporation to erect,
firm or
construct, enlarge, alter,
repair, move, improve, remove,
equip, use, occupy or maintain
structure in the city or cause
convert or demolish,
any building or
the same to be done,
contrary to or in violation of any of the provisions
of this code.
(b) Any person, firm or corporation violating any of the
provisions of the code shall be deemed guilty of a
misdemeanor, and each person shall be deemed guilty
of a separate offense for each and every day or
portion thereof during which any violation of any
of the provisions of this code is committed, con-
tinued or permitted, and upon conviction of any
such violation such person shall be punished by
a fine of not more than Three Hundred Dollars
($300.00), or by imprisonment for not more than
ninety (90) days, or by both such fine and
imprisonment."
Section 5. Description of Code
That the uniform Building Code, 1976 edition, and the Uniform
Building Code Standards, 1976 edition, hereinabove adopted by
reference, are designed to encourage development of better building
construction and public safety. Said code establishes administative
procedures for issuance of building permits; describes building
requirements based on the type of occupancy, location of fire zones
and types of construction; prescribes engineering regulations and
standards for fire protection; provides for types of wall and ceiling
coverings and construction of special structures.
-22-
RECORD OF PROCEEDINGS
100 Leaves
Section 6.
That three copies of the primary code and
considered for adoption by this ordinance, all
copies by the Mayor and City Council, shall be
Availability of copies for Public Inspection
secondary code being
certified to be true
on file with the
City Clerk and shall be open for public inspection in her office at
the Aspen City Hall, Aspen, Colorado, any weekday between the hours
of 9 A.M. and 5 P.M., at least fifteen days preceding the public
hearing on this ordinance.
Section 7. Certification on Adoption
That on passage of this ordinance, and adoption of these codes
by reference, one of the copies of the primary code and of each
secondary code may be kept in the office of the chief enforcement
officer instead of the office of the City Clerk. Following the
adoption of any of these codes, the City Clerk shall at all times
maintain a reasonable supply of copies of the primary code and of
any secondary codes incorporated in it by reference available for
purchase by the public.
Section 8. Repeal of Inconsistent Ordinances
That existing ordinances or parts of ordinances covering the
same matters as embraced in this ordinance are hereby repealed and
all ordinances or parts of ordinances inconsistent with the pro-
visions of this ordinance are hereby repealed, except that this
repeal shall not prevent the prosecution or punishment of any
person for any act done or committed in violation of any ordinance
hereby repealed prior to the taking effect of this ordinance.
Section 9. Partial Invalidity
If any provision of this ordinance or the application thereof
to any person or circumstance shall be found to be invalid, such
invalidity shall not affect any remaining portion or application
which can be given effect and to this end this ordinance is
declared to be severable.
-23-
RECORD OF PROCEEDINGS
100 Leaves
Section 10. Public Hearing
A public hearing on this ordinance shall be held on the ~
day of ~~-~ , 1977, at 5:00 P.M. in the
City Council Chambers, Aspen City Hall, Aspen, colorado. Pursuant
as amended
to Section 31-12-403, C.R.S. 1973/ notice of the hearing shall be
published at least twice, once at least eight (8) days preceding
the hearing and once at least fifteen (15) days preceding it.
INTRODUCED, READ AND ORDERED published as provided by law
by the City Council of the City of Aspen, Colorado, at its regular
meeting held at the City of Aspen on the ~ day of
ATTEST:
Kathryn S~/ Hauter
City Clerk
FINALLY adopted,
of
ATTEST:
passed and approved on the ~%~)day
-~t~cy ~tand%ey III /
Mayor/ C /
Kathryn ~. ' ~Ia~ter
City Clerk
-24-
RECORD OF PROCEEDINGS
100 Le~es
STATE OF COLORADO )
) ss
COUNTY OF PITKIN )
CERTIFICATE
I, Kathryn S. Haute'r, City clerk of Aspen, Colorado,
do hereby certify that the above and
introduced,
reading at
C~ty of Aspen on ~~~ , 197 7
foregoing ordinance was
read in full, and passed on ~
a regular meeting of the City Council of the
, and publish-
ed in the Aspen Times a weekly newspaper of general circul-
ation, published in the City of Aspen, Colorado, in its
issue of , 1977 , and was finally adopted
and approved at a regular meeting of the City Council on
Ordinance No. /~
, 197 2 , and ordered published as
, Series of 197 7, of said City, as
provided by law.
IN WITNESS WHEREOF, I have hereunto set my hand and
the seal of said City of Aspen, Colorado, this /~F~
day of .~_
, 197 7